VCC 1212-30 CI (3360)

Votronic VCC 1212-30 CI wiring diagram

Non-isolated 12V-to-12V booster with 30A output, a 20A limit setting and 39A maximum input. Article 3360 uses D+ or voltage activation and the included temperature sensor; its CI manual differs from the older 3324 VCC 1212-30.

Nominal voltage
12 V
Compatible systems
12 V
Continuous draw
39 A

Wiring diagram

How the VCC 1212-30 CI is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Votronic VCC 1212-30 CI wiring example with 3 components: Starter bank, VCC 1212-30 CI, House bank. 4 cable connections. Crossings are not junctions.Starter bank + to VCC 1212-30 CI START +: 6 AWG · 50 A fuse, 10 ft one way. VCC 1212-30 CI BORD + to House bank +: 6 AWG · 40 A fuse, 10 ft one way. Starter bank − to VCC 1212-30 CI IN −: 6 AWG, 10 ft one way. VCC 1212-30 CI OUT − to House bank −: 6 AWG, 10 ft one wayStarter bank + to VCC 1212-30 CI START +: 6 AWG · 50 A fuse, 10 ft one wayVCC 1212-30 CI BORD + to House bank +: 6 AWG · 40 A fuse, 10 ft one wayStarter bank − to VCC 1212-30 CI IN −: 6 AWG, 10 ft one wayVCC 1212-30 CI OUT − to House bank −: 6 AWG, 10 ft one way12 V 200 Ah starter bankStarter bank++−−Votronic VCC 1212-30 CI. The 3.048 m example runs use 16 mm², with 50 A protection at the starter-battery positive and 40 A at the house-battery positive. These choices follow Table 1 for the VCC 1212-30 CI, article 3360. Select the appropriate standard, EBL or existing-relay wiring scheme and configure charging and D+ control from the manual; the example does not simulate those controls.VCC 1212-30 CISTART +START +IN −IN −BORD +BORD +OUT −OUT −12 V 200 Ah house bankHouse bank++−−6 AWG · 50 A fuse6 AWG · 40 A fuse6 AWG6 AWG
Votronic VCC 1212-30 CI wiring example with 3 components: Starter bank, VCC 1212-30 CI, House bank. 4 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Cable labels are example values; use the equipment instructions and actual installation lengths.

The 3.048 m example runs use 16 mm², with 50 A protection at the starter-battery positive and 40 A at the house-battery positive. These choices follow Table 1 for the VCC 1212-30 CI, article 3360. Select the appropriate standard, EBL or existing-relay wiring scheme and configure charging and D+ control from the manual; the example does not simulate those controls. Manufacturer installation manual

Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

10 ft one way

12 V system

Wire
6 AWG · 16 mm²
Example fuse
40 A
Design current
30 A
Voltage drop
1.7%

Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

The 3.048 m example runs use 16 mm², with 50 A protection at the starter-battery positive and 40 A at the house-battery positive. These choices follow Table 1 for the VCC 1212-30 CI, article 3360. Select the appropriate standard, EBL or existing-relay wiring scheme and configure charging and D+ control from the manual; the example does not simulate those controls. Manufacturer installation manual

Show sizes in mm²

Supporting parts

  1. 20 ft total of 6 AWG (16 mm²) marine cable
  2. Terminations for 6 AWG cable, matched to the equipment's screw terminals, leads or studs
  3. 40 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. VCC 1212-30 CI article 3360; German April 2026 manual), checked 2026-10-01. Manufacturer documentation →

Which VCC version is this?

This is VCC 1212-30 CI, article 3360, not the earlier 3324 VCC 1212-30. The current manufacturer specification identifies a non-isolated 12 V booster with 30 A maximum output, a 20 A limit setting and 39 A maximum input.

How are power and protection arranged?

START + / IN − connect to the starter supply; BORD + / OUT − connect to the house system. The negatives are not galvanically isolated. If a shunt is fitted, bring system returns to its system side. Manual page 2 specifies 50 A input and 40 A output fuses, with 6, 10 or 16 mm² conductors according to its length table. Power-terminal torque is 1.2 Nm, small control terminals 0.5 Nm.

What must be configured?

Select the house-battery program before charging and install the supplied temperature sensor. D+ permits engine-controlled activation; leaving D+ open invokes voltage-based activation. Use the manual’s EBL/EVS diagram when integrating an existing electrical block: the extra starter-sensing terminal is not another high-current charger output.

What should commissioning prove?

Mount near the house bank with 10 cm clear ventilation space. Confirm charging starts with the intended engine signal and stops appropriately. Check battery-terminal voltage under load as well as indicator lights. The manual describes a small reverse maintenance-charge path, which some EBL configurations disable. Its behavior and lithium low-temperature handling must be checked against the CI instructions rather than an older VCC manual.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Non-isolated 12V-to-12V booster with 30A output, a 20A limit setting and 39A maximum input. Article 3360 uses D+ or voltage activation and the included temperature sensor; its CI manual differs from the older 3324 VCC 1212-30.

Nominal voltage
12 V
Compatible systems
12 V
Continuous draw
39 A
Rated output
30 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

START +

positive · input

39 A

IN −

negative · input

39 A

BORD +

positive · output

30 A

OUT −

negative · output

39 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11 — the US reference, and what Transport Canada accepts as an alternative to TP 1332 for pleasure craft under 24 m. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with VCC 1212-30 CI.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Free for up to 10 equipment components, with no account needed. Cables, busbars and fuse hardware do not count toward the limit. Your drawing saves in this browser. File exports are included with Crimp Pro.