Victron MultiPlus 24/5000

Model MultiPlus 24/5000/120-100

5000 VA inverter/charger at 24 V, 120 A charger, 100 A transfer switch + PowerAssist. Recommended DC protection 1× 400 A. 24 V banks only.

Open in Crimp →
Reference image unavailable
Victron MultiPlus 24/5000 · 6 terminals
01 — Wiring diagram

How the MultiPlus 24/5000 is wired

Victron MultiPlus 24/5000 wiring diagram WIRING DIAGRAM Victron MultiPlus 24/5000 wiring diagram 24 V battery bank Supplies this load MultiPlus 24/5000 Victron · MultiPlus 24/5000/1… 350 A 4/0 AWG (120 mm²) → DC + 4/0 AWG (120 mm²) → DC − 10 ft one way AC IN L AC IN N AC OUT L AC OUT N crimp.studio 200 A · 0.7% drop · ABYC E-11
Victron MultiPlus 24/5000 wiring diagram, 4/0 AWG (120 mm²) positive feed protected by a 350 A fuse and a matching negative return between the 24 V battery bank and the unit, plus AC IN L, AC IN N, AC OUT L, AC OUT N.

The run drawn here is the 10 ft reference run sized below. Sized against ABYC E-11 — the US reference, and what Transport Canada accepts as an alternative to TP 1332 for pleasure craft under 24 m. Confirm your own run length, routing and terminations before ordering — open this part in the designer to size it against your actual system.

02 — Reference run

What size cable and fuse does the MultiPlus 24/5000 need?

Conductor4/0 AWG120 mm²
Fuse350 Apositive run
Voltage drop0.7%10 ft one way
Design current200 A24 V system

Sized against ABYC E-11 — the US reference, and what Transport Canada accepts as an alternative to TP 1332 for pleasure craft under 24 m. The design current is the part's continuous draw. The Crimp engine applies its ordinary continuous-load headroom, voltage-drop budget, terminal clamp, and standard fuse ladder. The 10 ft one-way run is a stated reference, not a universal installation prescription.

03 — Catalog specification

Victron MultiPlus 24/5000 specifications and terminal map

Compatible systems
24 V
Rated power
4,000 W
Continuous draw
200 A
Rated output
120 A
Surge current
400 A

Terminal map

TerminalPolarityDirectionRating
AC IN Lneutralinput50 A
AC IN Nneutralinput50 A
DC +positiveinput400 A
DC −negativeinput400 A
AC OUT Lneutraloutput25 A
AC OUT Nneutraloutput25 A
04 — Supporting parts

What else you need to wire the MultiPlus 24/5000

  • 20 ft total of 4/0 AWG (120 mm²) marine cable
  • Four 4/0 AWG cable lugs matched to the equipment studs
  • 350 A fuse and holder on the positive run
  • Heat-shrink, strain relief, and terminal boots sized to the cable

Start from this part

Open the canvas with the MultiPlus 24/5000 already placed, then wire the rest of the system around it. Nothing to install and no sign-up — the project is saved in this browser, and you can download the file whenever you want it.

Open the canvas →

05 — Method & provenance

What is known, assumed, and computed.

Catalog profile

The manufacturer, model, ratings and terminal map are maintained as planning data in Crimp's component catalog. Confirm the current manufacturer manual, exact revision and installed nameplate before ordering or wiring.

Engine reference

Sized against ABYC E-11 — the US reference, and what Transport Canada accepts as an alternative to TP 1332 for pleasure craft under 24 m. The published conductor, fuse and voltage-drop result uses the visible reference length and current basis; it is not a universal installation prescription.

Read the complete methodology →
06 — Related components

Alternatives to the MultiPlus 24/5000

Browse all charger profiles →