Renogy DCC30S (RBC30D1S-G3/G4) wiring diagram

RBC30D1S-G3/G4 DCC30S: 30A dual-input charger for a 12V house bank, with 30V maximum solar input and 400W solar power. Hybrid charging is limited to 15A solar plus 15A alternator; the legacy G1 has a 25V solar limit.

Compatible systems
12 V
Rated output
30 A
PV open-circuit limit
30 V
Units

Wiring diagram

How the DCC30S G3/G4 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Renogy DCC30S (RBC30D1S-G3/G4) wiring example with 3 components: Starter bank, DCC30S G3/G4, House bank. 4 cable connections. Crossings are not junctions.Starter bank + to DCC30S G3/G4 ALT +: 6 mm² · 50 A fuse, 1 m one way. DCC30S G3/G4 OUT + to House bank +: 6 mm² · 40 A fuse, 1 m one way. Starter bank − to House bank −: 10 mm², 3 m one way. DCC30S G3/G4 NEG − to House bank −: 6 mm², 1 m one wayStarter bank + to DCC30S G3/G4 ALT +: 6 mm² · 50 A fuse, 1 m one wayDCC30S G3/G4 OUT + to House bank +: 6 mm² · 40 A fuse, 1 m one wayStarter bank − to House bank −: 10 mm², 3 m one wayDCC30S G3/G4 NEG − to House bank −: 6 mm², 1 m one way12 V 200 Ah starter bankStarter bank++−−Renogy DCC30S (RBC30D1S-G3/G4). G3/G4 vehicle-only example: 1 m leads, 50 A protection at the starter battery and 40 A at the house battery, following Renogy manual B5. Starter negative returns to house negative; the charger has one NEG− connection. Renogy's cable lengths include both conductors and its table specifies 150 °C copper cable. The example uses Crimp's cable model, so check the actual conductor, length and installation conditions. Solar, IGN and sensing are not connected.DCC30S G3/G4ALT +ALT +OUT +OUT +NEG −NEG −12 V 200 Ah house bankHouse bank++−−6 mm² · 50 A fuse6 mm² · 40 A fuse6 mm²
Renogy DCC30S (RBC30D1S-G3/G4) wiring example with 3 components: Starter bank, DCC30S G3/G4, House bank. 4 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.

G3/G4 vehicle-only example: 1 m leads, 50 A protection at the starter battery and 40 A at the house battery, following Renogy manual B5. Starter negative returns to house negative; the charger has one NEG− connection. Renogy's cable lengths include both conductors and its table specifies 150 °C copper cable. The example uses Crimp's cable model, so check the actual conductor, length and installation conditions. Solar, IGN and sensing are not connected. Manufacturer installation manual

Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

1 m one way

12 V system

Wire
6 mm² · 10 AWG
Example fuse
40 A
Design current
30 A
Voltage drop
0.8%

Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.

Already have a cable size? Check a simple copper run at your current and length with the DC voltage drop calculator in mm² or AWG.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

G3/G4 vehicle-only example: 1 m leads, 50 A protection at the starter battery and 40 A at the house battery, following Renogy manual B5. Starter negative returns to house negative; the charger has one NEG− connection. Renogy's cable lengths include both conductors and its table specifies 150 °C copper cable. The example uses Crimp's cable model, so check the actual conductor, length and installation conditions. Solar, IGN and sensing are not connected. Manufacturer installation manual

Supporting parts

  1. 2 m total of 6 mm² (10 AWG) marine cable
  2. Terminations for 6 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 40 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. B5 — February 27, 2026), checked 2026-11-25. Manufacturer documentation →

Which Renogy DCC30S is this?

This is the RBC30D1S-G3/G4, a 12 V, 30 A DC-DC battery charger with MPPT. Its solar input is limited to 30 V and 400 W. Check the generation on your unit: the legacy DCC30S G1 has a 25 V solar limit. The newer G5 is a separate revision and is not covered here.

How is the Renogy DCC30S G3/G4 wired?

Use ALT+ for starter-battery positive, PV+ for solar positive, OUT+ for house-battery positive and NEG− for house-battery negative. There are four power studs, not separate negative studs for each source.

Connect the charger to house negative first. Starter and solar negatives also return to house negative, as shown in Renogy's wiring diagram. The example follows this route with solar disconnected. IGN is for smart alternators; sensing and RS485 are outside the power drawing.

Which fuses and cables does the Renogy DCC30S G3/G4 need?

Manual B5 specifies 50 A at starter positive and 40 A at house positive. It places the starter fuse close to the battery, ideally within 20 cm. These replace the less specific guidance in B4; use B5's fuse table for this revision.

Its cable table uses the combined positive and negative length: 10 AWG up to 3 m, 8 AWG for 3–6 m and 6 AWG for 6–9 m. The table specifies copper cable rated above 150 °C. Crimp uses its own wire model; use the technical reference for this example and verify your actual cable and installation against the complete table.

What should I bear in mind with the Renogy DCC30S G3/G4?

  • Solar headroom: check array open-circuit voltage in cold weather against the 30 V limit. A panel's nominal “12 V” label is not its maximum voltage.
  • Hybrid charging: the weak-solar mode limits each source's charging contribution to 15 A, with 30 A total. Solar-only charging can use the full stage. See working logic.
  • Simulation limits: the shared-negative solar layout can simulate charging, but its solar cable-current estimates remain unverified. Starter-battery top-up from solar, ignition thresholds, temperature derating and BMS control are not fully modeled.

What do owners and installers say about the Renogy DCC30S G3/G4?

Generation matters when comparing reports: DCC30S discussions can describe the older 25 V unit. No generation-specific owner pattern is established here. For a unit that will not charge, Renogy's troubleshooting guide walks through battery settings, fuses, terminal voltages and indicators; use the G3/G4 manual for the thresholds.

What belongs around the Renogy DCC30S G3/G4?

Plan the starter battery, house bank, both battery fuses and complete negative return. Add solar only after checking its voltage and power. Use the DC-DC charger calculator to compare charging capacity, or the wire-size calculator for a separate cable run. In Crimp's component picker, search RBC30D1S-G3; edit the example above to enter your actual equipment and lengths.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

RBC30D1S-G3/G4 DCC30S: 30A dual-input charger for a 12V house bank, with 30V maximum solar input and 400W solar power. Hybrid charging is limited to 15A solar plus 15A alternator; the legacy G1 has a 25V solar limit.

Compatible systems
12 V
Rated output
30 A
PV open-circuit limit
30 V

Terminal map

Four power studs: ALT+ for the starter battery, PV+ for solar, OUT+ for the house battery and one shared NEG−. Connect NEG− to house negative first; solar and starter negatives also return to house negative. Check the full generation code: G3/G4 allows 30 V PV; G1 allows 25 V.

ALT +

positive · input

—

PV +

positive · input

—

OUT +

positive · output

30 A

NEG −

negative · bidi

30 A

A dash means a current rating is not specified here.

Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.