RNG-INVT-2000-12V-P2-US

Renogy P2 2000W 12V Inverter wiring diagram

2000W pure sine inverter with 115VAC/60Hz output and a 4000W one-second AC surge rating. Planning draw is calculated at 196.1A using 12V and 85% full-load efficiency; lower battery voltage increases demand. DC terminal bounds use its 250A fuse recommendation, not a verified connector rating. This P2 is not an inverter/charger or a UPS transfer-switch model.

Nominal voltage
12 V
Compatible systems
12 V
Rated power
2,000 W

Wiring diagram

How the P2 2000W is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Renogy P2 2000W 12V Inverter wiring example with 3 components: House bank, Battery disconnect, P2 2000W. 3 cable connections. Crossings are not junctions.Battery disconnect B to P2 2000W DC +: 2/0 AWG · 250 A fuse, 10 ft one way. House bank − to P2 2000W DC −: 2/0 AWG, 10 ft one way. House bank + to Battery disconnect A: 2/0 AWG · 250 A fuse, 1.0 ft one wayBattery disconnect B to P2 2000W DC +: 2/0 AWG · 250 A fuse, 10 ft one wayHouse bank − to P2 2000W DC −: 2/0 AWG, 10 ft one wayHouse bank + to Battery disconnect A: 2/0 AWG · 250 A fuse, 1.0 ft one way12 V 200 Ah house bankHouse bank++−−Main Battery SwitchBattery disconnectABRenogy P2 2000W 12V Inverter. The DC example uses Renogy's 250 A battery fuse. Its 196.1 A design demand is calculated from 2000 W at 12 V and 85% efficiency, not a measured draw. Lower battery voltage increases demand. Check actual cable length, battery/BMS capability, DC connections and the manual's installation requirements; AC outlets, protective earth and appliance starting loads need separate review.P2 2000WDC +DC +DC −DC −2/0 AWG · 250 A fuse2/0 AWG2/0 AWG · 250 A fuse
Renogy P2 2000W 12V Inverter wiring example with 3 components: House bank, Battery disconnect, P2 2000W. 3 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Cable labels are example values; use the equipment instructions and actual installation lengths.

The DC example uses Renogy's 250 A battery fuse. Its 196.1 A design demand is calculated from 2000 W at 12 V and 85% efficiency, not a measured draw. Lower battery voltage increases demand. Check actual cable length, battery/BMS capability, DC connections and the manual's installation requirements; AC outlets, protective earth and appliance starting loads need separate review. Manufacturer installation manual

Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

10 ft one way

12 V system

Wire
2/0 AWG · 70 mm²
Example fuse
250 A
Design current
196.1 A
Voltage drop
2.5%

Sized against ABYC E-11. The design current is a catalog planning estimate for inverter operation at nominal battery voltage, not a measured draw. Actual current changes with load, battery voltage and efficiency. Check the exact model's cable, fuse and installation requirements. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

The DC example uses Renogy's 250 A battery fuse. Its 196.1 A design demand is calculated from 2000 W at 12 V and 85% efficiency, not a measured draw. Lower battery voltage increases demand. Check actual cable length, battery/BMS capability, DC connections and the manual's installation requirements; AC outlets, protective earth and appliance starting loads need separate review. Manufacturer installation manual

Show sizes in mm²

Supporting parts

  1. 20 ft total of 2/0 AWG (70 mm²) marine cable
  2. Terminations for 2/0 AWG cable, matched to the equipment's screw terminals, leads or studs
  3. 250 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. Pure Sine Wave Inverter manual February 2023 A2; RNG-INVT-2000-12V-P2), checked 2026-10-01. Manufacturer documentation →

What does this P2 provide?

The US P2 2000 W produces 115 V / 60 Hz AC from a 12 V battery and offers a 4000 W, one-second AC surge. It has no charger or shore-transfer input. Do not use wiring instructions for Renogy’s PUH/UPS or inverter-charger models.

Which current does the planner use?

Manual pages 29–30 list 166.6 A battery current, exactly 2000 W ÷ 12 V, while separately specifying greater than 85% full-load efficiency. That current row omits conversion losses. The catalog therefore uses a labeled 196.1 A planning estimate: 2000 ÷ (12 × 0.85). Actual current depends on battery voltage and load; lower voltage requires more current. No independent terminal ampacity or DC surge is inferred from the fuse.

What connections and protection are needed?

Connect the battery through an external disconnect and the manual’s 250 A battery fuse, checking conductor ampacity and route. Printed page 21 gives 14 ±0.5 Nm at the DC terminals. Connect the chassis grounding point and wire AC loads only to the AC output; receptacles and terminal-block loads share the same total rating.

How is it started and checked?

Start with AC loads switched off, energize the inverter, then add loads while checking battery voltage at its terminals. Set the switch to REM when using the wired remote. A low-voltage alarm under load can indicate cable drop even when resting battery voltage looks healthy. Keep ventilation clear and isolate both sides before servicing: the off switch does not discharge internal capacitors immediately.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

2000W pure sine inverter with 115VAC/60Hz output and a 4000W one-second AC surge rating. Planning draw is calculated at 196.1A using 12V and 85% full-load efficiency; lower battery voltage increases demand. DC terminal bounds use its 250A fuse recommendation, not a verified connector rating. This P2 is not an inverter/charger or a UPS transfer-switch model.

Nominal voltage
12 V
Compatible systems
12 V
Rated power
2,000 W
Estimated DC draw
196.1 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

DC +

positive · input

250 A

DC −

negative · input

250 A

AC L

neutral · output

16.6 A

AC N

neutral · output

16.6 A

GROUND

ground · bidi

—

A dash means a current rating is not specified here.

Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11 — the US reference, and what Transport Canada accepts as an alternative to TP 1332 for pleasure craft under 24 m. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with P2 2000W.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Free for up to 10 equipment components, with no account needed. Cables, busbars and fuse hardware do not count toward the limit. Your drawing saves in this browser. File exports are included with Crimp Pro.