Editable DC examples

Campervan & RV 12 V wiring diagrams

A simple campervan wiring diagram with solar, a leisure battery, lights and a Maxxfan. The expanded RV solar wiring diagram adds alternator charging through an Orion XS B2B charger.

Primary units

Simple solar and DC loads

6 components · 10 conductors · 12 V house system

Open this example in Crimp →
Campervan example — solar and DC loadsHouse / auxiliary bankPlanning placeholder+BS 50265026IN +IN −1 +2 +1 −2 −Cabin lightsPlanning placeholder+MaxxfanMaxxfan Deluxe 7500K+Reference solar arrayPlanning placeholder+MPPT 100/50SmartSolar 100/50PV +PV −BATT +BATT −C1C2C3C4C5C6C7C8C9C10

Solid red = positive · dashed dark = return. Shared routes show both styles. Cable IDs match the schedule. Only connected terminals are drawn; crossings are not junctions. Scroll the drawing sideways on a small screen. Read the assumptions before adapting it.

Protection is unfinished. The shown fuse ratings do not select an exact protective device or locate it at the battery. Battery-end placement and unspecified-fuse warnings remain in Crimp. All charging and load currents below are design allowances, not measured operating currents.

Current engine findings

The blade-fuse interrupt check uses the engine’s chemistry-based fault-current assumption. This is not measured fault current. Resolve the bank and protection design before installation.

Check the exact fuse, holder and battery evidence →
  • critical: ATC fuse can't interrupt this battery's fault current (C3)
  • critical: ATC fuse can't interrupt this battery's fault current (C5)
  • warning: Fuse on House / auxiliary bank+ is too far from the battery (C1, C9)
  • warning: House / auxiliary bank (LFP) has no fuse on the positive post (system)
  • warning: 2 fused runs don't say which type of fuse (C1, C9)
Cable table — every displayed connection

Each length is one way. Drop is the engine’s run estimate including return, not a measured end-to-end system result; shared legs can have different conservative design-current bounds. “Pinned” marks a manufacturer-based example choice to review after edits. AWG is approximate; retain the stated conductor area when selecting actual wire.

Simple solar and DC loads cable schedule in metric with AWG
C1 · House / auxiliary bank +
↔ Blue Sea 5026 ST Blade Fuse Block IN +
One-way length1 m3.3 ftConductor2.5 mm²AWG 13 · 35 A tableDesign current7 AFuse10 ADrop / allowance0.82% / 3%
C2 · House / auxiliary bank −
↔ Blue Sea 5026 ST Blade Fuse Block IN −
One-way length1 m3.3 ftConductor2.5 mm²AWG 13 · 35 A tableDesign current7 AFuseUnfused returnDrop / allowance0.82% / 3%
C3 · Blue Sea 5026 ST Blade Fuse Block 1 +
↔ Cabin lights +
One-way length3 m9.8 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current2 AFuse3 ADrop / allowance1.17% / 10%
C4 · Blue Sea 5026 ST Blade Fuse Block 1 −
↔ Cabin lights −
One-way length3 m9.8 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current2 AFuseUnfused returnDrop / allowance1.17% / 10%
C5 · Blue Sea 5026 ST Blade Fuse Block 2 +
↔ Maxxfan Deluxe 7500K +
One-way length2 m6.6 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current5 AFuse7.5 ADrop / allowance1.94% / 3%
C6 · Blue Sea 5026 ST Blade Fuse Block 2 −
↔ Maxxfan Deluxe 7500K −
One-way length2 m6.6 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current5 AFuseUnfused returnDrop / allowance1.94% / 3%
C7 · Reference solar array +
↔ SmartSolar MPPT 100/50 PV +
One-way length3 m9.8 ftConductor4 mm²AWG 11 · 45 A tableDesign current20 AFusePV: review string protectionDrop / allowance2.63% / 3%
C8 · Reference solar array −
↔ SmartSolar MPPT 100/50 PV −
One-way length3 m9.8 ftConductor4 mm²AWG 11 · 45 A tableDesign current20 AFuseUnfused returnDrop / allowance2.63% / 3%
C9 · SmartSolar MPPT 100/50 BATT +
↔ House / auxiliary bank +
One-way length1 m3.3 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuse70 ADrop / allowance0.91% / 3%
C10 · SmartSolar MPPT 100/50 BATT −
↔ House / auxiliary bank −
One-way length1 m3.3 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuseUnfused returnDrop / allowance0.91% / 3%
Component table and exact example assumptions
Components in Simple solar and DC loads
House / auxiliary bankPlanning placeholder

12 V · 200 Ah

12 V, 200 Ah planning placeholder. Select an actual bank, compatible BMS, charge/discharge limits and battery-end protection. Ah does not select the fuse. Planning example, not installation approval. Batteries, the PV array and unnamed loads are placeholders. Battery acceptance, BMS controls, low-temperature charging, short-circuit current and runtime have not been verified. Fuse ratings are preliminary cable protection or stated manufacturer choices. Exact fuse/holder, DC voltage, interrupt rating and battery-end placement still need verification. Cable fuses have no physical placement here; the editor retains its battery-protection warnings. Lengths are physical one-way conductor runs. Voltage drop includes a return; shared paths use the engine’s conservative current bounds, not a prediction of simultaneous power flow. The calculation does not verify unequal shared-return lengths as one complete circuit. AWG labels are approximate table counterparts to metric conductors, not identical cross-sectional areas. Sizing uses Crimp’s ABYC-based tables for 105°C copper outside engine spaces, with no additional heat or bundling derating in these examples. Explicit 3% circuit targets and 10% cabin-light allowances are planning choices; terminals on placeholders carry generic planning limits, not verified connector ratings. US RV, UK campervan and Australian 4WD wording does not establish UK or AS/NZS installation compliance.
Blue Sea 5026 ST Blade Fuse Block5026Blue Sea 5026: 12 ATO/ATC branches, 100 A maximum block total, 30 A maximum per branch, 32 V DC. Only two branches used. Input feed protection is separate; fuses are sold separately. Source: Blue Sea 5026 product page and wiring schematic, checked 2026-09-11.
Cabin lightsPlanning placeholder

12 V · 2 A load allowance

2 A continuous planning allowance. No measured duty cycle or energy budget.
Maxxfan Deluxe 7500KMaxxfan Deluxe 7500K

5 A load allowance

5 A minimum supply-service allowance from Airxcel 11E90001K (11-2017), not measured draw or startup current. Tagged black lead is positive. External fuse rating is a preliminary cable-protection choice.
Reference solar arrayPlanning placeholder

20 V · 20 A rated / planning output · 400 W · 24 V STC Voc

400 W / 20 V operating / 24 V STC Voc placeholder, not a selected panel. Actual Isc, cold Voc, temperature coefficient, string fuses and PV isolation must be checked. No yield claim.
SmartSolar MPPT 100/50SmartSolar 100/50

50 A rated / planning output

SmartSolar 100/50, manual rev 12 (06/2026). Battery circuit sized at rated 50 A, not the reference array’s predicted output. 70 A example fuse is within the 55–70 A battery range; 16 mm² cable choice and 1 m battery run. Connect battery first, wait 10 seconds, check voltage, then connect PV. Configure the actual battery profile.

Solar plus alternator charging

8 components · 14 conductors · 12 V house system

Open this example in Crimp →
Campervan example — solar and alternatorHouse / auxiliary bankPlanning placeholder+BS 50265026IN +IN −1 +2 +1 −2 −Cabin lightsPlanning placeholder+MaxxfanMaxxfan Deluxe 7500K+Reference solar arrayPlanning placeholder+MPPT 100/50SmartSolar 100/50PV +PV −BATT +BATT −AGM starter bankPlanning placeholder+Orion XS 50AOrion XS 12/12-50AIN +IN −OUT +OUT −C1C2C3C4C5C6C7C8C9C10C11C12C13C14

Solid red = positive · dashed dark = return. Shared routes show both styles. Cable IDs match the schedule. Only connected terminals are drawn; crossings are not junctions. Scroll the drawing sideways on a small screen. Read the assumptions before adapting it.

Protection is unfinished. The shown fuse ratings do not select an exact protective device or locate it at the battery. Battery-end placement and unspecified-fuse warnings remain in Crimp. All charging and load currents below are design allowances, not measured operating currents.

Both chargers may charge the same bank. Verify their combined limit against the battery/BMS; the array does not guarantee the MPPT’s full rated output. Charger controls and a load disconnect are not modeled.

Current engine findings

The blade-fuse interrupt check uses the engine’s chemistry-based fault-current assumption. This is not measured fault current. Resolve the bank and protection design before installation.

Check the exact fuse, holder and battery evidence →
  • critical: ATC fuse can't interrupt this battery's fault current (C3)
  • critical: ATC fuse can't interrupt this battery's fault current (C5)
  • warning: Fuse on House / auxiliary bank+ is too far from the battery (C1, C9, C13)
  • warning: Fuse on AGM starter bank+ is too far from the battery (C11)
  • warning: House / auxiliary bank (LFP) has no fuse on the positive post (system)
  • warning: 3 fused runs don't say which type of fuse (C1, C9, C13)
Cable table — every displayed connection

Each length is one way. Drop is the engine’s run estimate including return, not a measured end-to-end system result; shared legs can have different conservative design-current bounds. “Pinned” marks a manufacturer-based example choice to review after edits. AWG is approximate; retain the stated conductor area when selecting actual wire.

Solar plus alternator charging cable schedule in metric with AWG
C1 · House / auxiliary bank +
↔ Blue Sea 5026 ST Blade Fuse Block IN +
One-way length1 m3.3 ftConductor2.5 mm²AWG 13 · 35 A tableDesign current7 AFuse10 ADrop / allowance0.82% / 3%
C2 · House / auxiliary bank −
↔ Blue Sea 5026 ST Blade Fuse Block IN −
One-way length1 m3.3 ftConductor2.5 mm²AWG 13 · 35 A tableDesign current7 AFuseUnfused returnDrop / allowance0.82% / 3%
C3 · Blue Sea 5026 ST Blade Fuse Block 1 +
↔ Cabin lights +
One-way length3 m9.8 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current2 AFuse3 ADrop / allowance1.17% / 10%
C4 · Blue Sea 5026 ST Blade Fuse Block 1 −
↔ Cabin lights −
One-way length3 m9.8 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current2 AFuseUnfused returnDrop / allowance1.17% / 10%
C5 · Blue Sea 5026 ST Blade Fuse Block 2 +
↔ Maxxfan Deluxe 7500K +
One-way length2 m6.6 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current5 AFuse7.5 ADrop / allowance1.94% / 3%
C6 · Blue Sea 5026 ST Blade Fuse Block 2 −
↔ Maxxfan Deluxe 7500K −
One-way length2 m6.6 ftConductor1.5 mm²AWG 16 · 25 A tableDesign current5 AFuseUnfused returnDrop / allowance1.94% / 3%
C7 · Reference solar array +
↔ SmartSolar MPPT 100/50 PV +
One-way length3 m9.8 ftConductor4 mm²AWG 11 · 45 A tableDesign current20 AFusePV: review string protectionDrop / allowance2.63% / 3%
C8 · Reference solar array −
↔ SmartSolar MPPT 100/50 PV −
One-way length3 m9.8 ftConductor4 mm²AWG 11 · 45 A tableDesign current20 AFuseUnfused returnDrop / allowance2.63% / 3%
C9 · SmartSolar MPPT 100/50 BATT +
↔ House / auxiliary bank +
One-way length1 m3.3 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuse70 ADrop / allowance0.91% / 3%
C10 · SmartSolar MPPT 100/50 BATT −
↔ House / auxiliary bank −
One-way length1 m3.3 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuseUnfused returnDrop / allowance0.91% / 3%
C11 · AGM starter bank +
↔ Orion XS 12/12-50A IN +
One-way length3 m10 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuse60 ADrop / allowance2.78% / 3%
C12 · AGM starter bank −
↔ Orion XS 12/12-50A IN −
One-way length3 m10 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuseUnfused returnDrop / allowance2.78% / 3%
C13 · Orion XS 12/12-50A OUT +
↔ House / auxiliary bank +
One-way length1 m3.3 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuse60 ADrop / allowance0.91% / 3%
C14 · Orion XS 12/12-50A OUT −
↔ House / auxiliary bank −
One-way length1 m3.3 ftConductor16 mm²AWG 6 · 120 A tablePinned choiceDesign current50 AFuseUnfused returnDrop / allowance0.91% / 3%
Component table and exact example assumptions
Components in Solar plus alternator charging
House / auxiliary bankPlanning placeholder

12 V · 200 Ah

12 V, 200 Ah planning placeholder. Select an actual bank, compatible BMS, charge/discharge limits and battery-end protection. Ah does not select the fuse. Planning example, not installation approval. Batteries, the PV array and unnamed loads are placeholders. Battery acceptance, BMS controls, low-temperature charging, short-circuit current and runtime have not been verified. Fuse ratings are preliminary cable protection or stated manufacturer choices. Exact fuse/holder, DC voltage, interrupt rating and battery-end placement still need verification. Cable fuses have no physical placement here; the editor retains its battery-protection warnings. Lengths are physical one-way conductor runs. Voltage drop includes a return; shared paths use the engine’s conservative current bounds, not a prediction of simultaneous power flow. The calculation does not verify unequal shared-return lengths as one complete circuit. AWG labels are approximate table counterparts to metric conductors, not identical cross-sectional areas. Sizing uses Crimp’s ABYC-based tables for 105°C copper outside engine spaces, with no additional heat or bundling derating in these examples. Explicit 3% circuit targets and 10% cabin-light allowances are planning choices; terminals on placeholders carry generic planning limits, not verified connector ratings. US RV, UK campervan and Australian 4WD wording does not establish UK or AS/NZS installation compliance.
Blue Sea 5026 ST Blade Fuse Block5026Blue Sea 5026: 12 ATO/ATC branches, 100 A maximum block total, 30 A maximum per branch, 32 V DC. Only two branches used. Input feed protection is separate; fuses are sold separately. Source: Blue Sea 5026 product page and wiring schematic, checked 2026-09-11.
Cabin lightsPlanning placeholder

12 V · 2 A load allowance

2 A continuous planning allowance. No measured duty cycle or energy budget.
Maxxfan Deluxe 7500KMaxxfan Deluxe 7500K

5 A load allowance

5 A minimum supply-service allowance from Airxcel 11E90001K (11-2017), not measured draw or startup current. Tagged black lead is positive. External fuse rating is a preliminary cable-protection choice.
Reference solar arrayPlanning placeholder

20 V · 20 A rated / planning output · 400 W · 24 V STC Voc

400 W / 20 V operating / 24 V STC Voc placeholder, not a selected panel. Actual Isc, cold Voc, temperature coefficient, string fuses and PV isolation must be checked. No yield claim.
SmartSolar MPPT 100/50SmartSolar 100/50

50 A rated / planning output

SmartSolar 100/50, manual rev 12 (06/2026). Battery circuit sized at rated 50 A, not the reference array’s predicted output. 70 A example fuse is within the 55–70 A battery range; 16 mm² cable choice and 1 m battery run. Connect battery first, wait 10 seconds, check voltage, then connect PV. Configure the actual battery profile.
AGM starter bankPlanning placeholder

12 V · 80 Ah

12 V AGM source placeholder. Engine cranking and alternator are outside this drawing. No vehicle input headroom, idle output or factory wiring has been verified. Dedicated logical return: use the vehicle’s designated ground point where required by battery current sensing.
Orion XS 12/12-50AOrion XS 12/12-50A

50 A rated / planning output

Non-isolated Orion XS 12/12-50A, rev 11 (06/2026). Logical IN− and OUT− represent its single physical GND terminal. Input/output limits are each up to 50 A; full output is not guaranteed at low input voltage. 60 A battery fuses and 16 mm² conductors are pinned choices. Remote/BMS control, charge profile, engine detection and alternator headroom require review.

Before adapting an example

What these drawings assume

These camper van and RV examples cover the 12 V DC house system. AC shore supply, inverter circuits, protective earth and mains distribution are outside the drawing. This is an editable circuit example, not a full electrical or energy calculator: battery capacity and solar yield still need your daily loads, climate and charging schedule.

  • Planning example, not installation approval. Batteries, the PV array and unnamed loads are placeholders. Battery acceptance, BMS controls, low-temperature charging, short-circuit current and runtime have not been verified.
  • Fuse ratings are preliminary cable protection or stated manufacturer choices. Exact fuse/holder, DC voltage, interrupt rating and battery-end placement still need verification. Cable fuses have no physical placement here; the editor retains its battery-protection warnings.
  • Lengths are physical one-way conductor runs. Voltage drop includes a return; shared paths use the engine’s conservative current bounds, not a prediction of simultaneous power flow. The calculation does not verify unequal shared-return lengths as one complete circuit. AWG labels are approximate table counterparts to metric conductors, not identical cross-sectional areas.
  • Sizing uses Crimp’s ABYC-based tables for 105°C copper outside engine spaces, with no additional heat or bundling derating in these examples. Explicit 3% circuit targets and 10% cabin-light allowances are planning choices; terminals on placeholders carry generic planning limits, not verified connector ratings. US RV, UK campervan and Australian 4WD wording does not establish UK or AS/NZS installation compliance.

For an inverter upgrade, read the single-120 V MultiPlus-II example. Its manual requires parallel DC cables; Crimp’s single-conductor calculation does not verify that pair. It is not part of either diagram here.

Adding monitoring or larger distribution changes the current paths. Read the SmartShunt return-path example and Lynx Distributor example, including their conservative series-current bounds and unresolved protection. The model pages keep those limitations visible.

Keep goingWire size calculatorEnter one-way length, current and installation conditions to compare ampacity and voltage drop.Keep goingDC-DC charger size calculatorCheck vehicle headroom and battery acceptance before choosing a charging current.Keep going12 V boat wiring diagramsA small solar house system and a separate starter/house-bank charging example.Keep going12 V dual battery wiring diagramsStarter-to-auxiliary charging with Orion XS or REDARC BCDC1240D, plus protected house loads.Keep goingLiFePO₄ fuse size calculatorCheck exact fuse/holder, voltage, whole-bank fault current and placement evidence.Keep goingLead-acid to LiFePO₄ conversion guideReview charging, protection and monitoring when changing battery chemistry.Keep goingSizing methodologyRead the engine’s ABYC assumptions and limits before adapting an example.