Blue Sea Systems · 7184

Blue Sea 285-Series 60A Breaker wiring diagram

Surface-mount 60A thermal DC breaker, rated to 48VDC with 3000A interrupt capacity at 48V. Manual reset, trip-free operation and M6 studs. Its 60A rating is circuit protection, not the load current; do not operate it as a switch into high-inrush loads.

Compatible systems
12 V / 24 V / 48 V

Wiring diagram

How the 285-Series 60A is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Blue Sea 285-Series 60A Breaker wiring example with 3 components: House bank, 285-Series 60A, Reference load. 3 cable connections. Crossings are not junctions.House bank + to 285-Series 60A LINE: 8 AWG · 25 A fuse, 10 ft one way. 285-Series 60A LOAD to Reference load +: 8 AWG · 25 A fuse, 10 ft one way. House bank − to Reference load −: 8 AWG, 10 ft one wayHouse bank + to 285-Series 60A LINE: 8 AWG · 25 A fuse, 10 ft one way285-Series 60A LOAD to Reference load +: 8 AWG · 25 A fuse, 10 ft one wayHouse bank − to Reference load −: 8 AWG, 10 ft one way12 V 200 Ah house bankHouse bank++−−Blue Sea 285-Series 60A Breaker285-Series 60ALINELOAD12 V reference loadReference load++−−8 AWG · 25 A fuse8 AWG · 25 A fuse8 AWG
Blue Sea 285-Series 60A Breaker wiring example with 3 components: House bank, 285-Series 60A, Reference load. 3 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Cable labels are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

Cable sizes depend on the connected equipment, current and cable lengths. Add those details in Crimp to size each run.

View diagram in mm²

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. 7184 official product specifications and 285-Series dimensioned drawing; no linked installation manual), checked 2026-10-01. Manufacturer documentation →

What does the 60 A rating mean?

The 7184 is a surface-mounted, manually reset 60 A thermal breaker for circuits up to 48 V DC. Its manufacturer specification gives 3000 A interrupt capacity at 48 V. The 60 A value is circuit protection, not the equipment’s operating current; do not use it as the load in an energy budget.

How is it connected?

Install it in the protected positive feed and keep the source-side unprotected cable appropriately short. It uses M6 studs, accepting 1/4-inch ring terminals, with 5.65 Nm published stud torque. Support the cables so their weight does not twist the studs or case. The official dimension drawing supplies mounting dimensions; Blue Sea links no separate installation manual for this SKU.

How do you check suitability?

Check load current, conductor ampacity, system voltage and available fault current independently. A thermal trip is affected by temperature and duration; it is not a precision current limiter. Do not assume its interrupt rating is sufficient for every lithium bank merely because the operating voltage is 12 V.

What happens after a trip?

The lever displays the open condition and the mechanism is trip-free. Find the overload or wiring fault before resetting. Blue Sea permits switching use but excludes switching into high-inrush loads; use an appropriate disconnect/precharge arrangement where required. Repeated tripping should prompt current, connection-temperature and cable checks, not an automatic upgrade to a larger breaker.

How is the installed breaker recorded?

Set the protected cable’s protection override to 60 A to record this hardware rating. The component’s name and switch symbol alone do not establish a 60 A protection setting in the planner. Check the actual breaker’s interrupt rating and trip curve separately; the software does not simulate its thermal trip timing.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Surface-mount 60A thermal DC breaker, rated to 48VDC with 3000A interrupt capacity at 48V. Manual reset, trip-free operation and M6 studs. Its 60A rating is circuit protection, not the load current; do not operate it as a switch into high-inrush loads.

Compatible systems
12 V / 24 V / 48 V

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

LINE

positive · bidi

60 A

LOAD

positive · bidi

60 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Cable labels apply to the connected example, not a fixed cable size for this component. Set your actual equipment, current, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works