12 V · 24 V DC branch circuits · mm² and AWG

Fuse size calculator

Enter the load’s current and the cable you are using to get a standard fuse rating that won’t blow in normal use and still protects the wire. Free, no sign-up.

Cable sizes

The most it draws for longer than a moment.

Optional. Motors, compressors, inverters.

The cable this fuse protects.

The hottest part of the route.

Example inputs. Change any value to size your fuse.

Standard fuse rating

25 A fuse

Protects 6 mm² (up to 60 A would too)

Minimum rating (1.25 × running current)
25 A
Ampacity of 6 mm²
60 A
Largest fuse this cable allows
60 A

Fit it at the source end of the positive cable. Check the fuse’s DC voltage and interrupt ratings, and the equipment manual’s own fuse figure.

Draw the whole system in Crimp

The editor sizes every cable and fuse as you connect parts, and checks the battery fuse, holder and placement too.

Fuse size chart

Fuse rating and smallest cable by load current

For a continuous load on cable outside engine spaces. The cable column is the smallest conductor that can host the fuse; a long run can need a larger one for voltage drop.

Standard fuse rating and smallest copper cable for each continuous load current
Load currentFuseSmallest cable (mm²)Smallest cable (AWG)
1 A2 A1.5 mm²14 AWG
2 A3 A1.5 mm²14 AWG
3 A5 A1.5 mm²14 AWG
5 A7.5 A1.5 mm²14 AWG
8 A10 A1.5 mm²14 AWG
10 A15 A1.5 mm²14 AWG
12 A15 A1.5 mm²14 AWG
15 A20 A1.5 mm²14 AWG
20 A25 A1.5 mm²14 AWG
25 A35 A2.5 mm²12 AWG
30 A40 A4 mm²10 AWG
40 A50 A6 mm²8 AWG
50 A70 A10 mm²6 AWG
60 A80 A10 mm²6 AWG
80 A100 A16 mm²4 AWG
100 A125 A25 mm²2 AWG
150 A200 A35 mm²1 AWG
200 A250 A70 mm²3/0 AWG

Check the length with the voltage drop table. Where an equipment manual names a fuse, use the manufacturer’s figure.

Method

How the fuse rating is chosen

Fuse ≥ 1.25 × running current, and fuse ≤ cable ampacity

The lower bound keeps the fuse from blowing at the load’s normal current: 25% headroom for a continuous load. A start-up surge raises it only when the surge is more than 1.5 times the fuse rating, because DC fuses carry a brief overload for long enough to start a motor. That factor is Crimp’s planning assumption; the exact fuse’s time-current curve is the real test.

The upper bound is the cable’s ampacity, because the fuse is there to protect the wire. Ampacities come from ABYC E-11 TABLE VI-A for 105 °C copper outside engine spaces, with the engine-space multiplier of 0.82 at 50 °C. This is the same rule and table the editor uses when it fuses a cable you draw.

If no standard rating fits between the two, the calculator says the cable is too small rather than offering a fuse that would blow, or one too large to protect the wire.

What this calculator does not check

The fuse’s DC voltage rating and interrupt rating, the holder’s own current limit and derating, and where the fuse sits. A battery fuse also has to interrupt the battery’s full short-circuit current: use the LiFePO₄ battery fuse check for that.

Starter motor (cranking) cables follow different rules. Bundled cables, conduit and higher temperatures carry less current than the table assumes.

Common questions

Fuse size questions

How do I work out what size fuse I need?

Multiply the continuous current by 1.25 and round up to the next standard fuse rating. Then check the cable: the fuse must not be larger than the cable's ampacity, because the fuse is there to protect the wire. A 20 A load gets a 25 A fuse, which 1.5 mm² or 14 AWG copper (25 A ampacity outside engine spaces) or larger can host.

Should the fuse match the device or the wire?

Both. The rating must be high enough not to blow at the device's normal current and surge, and no higher than the cable's ampacity. If no standard rating does both, the cable is too small for the load.

What size fuse for a 12 V fridge drawing 5 A?

5 A × 1.25 = 6.25 A, so the next standard rating is 7.5 A, on 1.5 mm² or 14 AWG cable or larger. Many fridge manuals name a fuse; use the manufacturer's figure when it gives one. Dometic's CRX 50/65 manual, for example, specifies 15 A at 12 V.

Where should the fuse go?

At the source end of the positive cable, as close to the battery or bus as practical. ABYC E-11 normally allows at most 175 mm (7 in) of unprotected cable between the source and the fuse.

Does this work for a starter motor cable?

No. Cranking circuits are treated differently: they are exempt from the ampacity limit and need a fuse that tolerates the cranking surge, if they are fused at all. Use the engine manufacturer's guidance.

Keep goingVoltage drop calculatorCheck the cable you have against current and run length.Keep goingWire size calculatorChoose a conductor from ampacity and voltage drop together.Keep goingLiFePO₄ battery fuse checkMain battery fuse: holder, DC voltage rating and whole-bank fault current.Keep goingWhat Crimp checksThe protection checks the editor runs on a whole drawing.