Fuse ≥ 1.25 × running current, and fuse ≤ cable ampacity
The lower bound keeps the fuse from blowing at the load’s normal current: 25% headroom for a continuous load. A start-up surge raises it only when the surge is more than 1.5 times the fuse rating, because DC fuses carry a brief overload for long enough to start a motor. That factor is Crimp’s planning assumption; the exact fuse’s time-current curve is the real test.
The upper bound is the cable’s ampacity, because the fuse is there to protect the wire. Ampacities come from ABYC E-11 TABLE VI-A for 105 °C copper outside engine spaces, with the engine-space multiplier of 0.82 at 50 °C. This is the same rule and table the editor uses when it fuses a cable you draw.
If no standard rating fits between the two, the calculator says the cable is too small rather than offering a fuse that would blow, or one too large to protect the wire.
What this calculator does not check
The fuse’s DC voltage rating and interrupt rating, the holder’s own current limit and derating, and where the fuse sits. A battery fuse also has to interrupt the battery’s full short-circuit current: use the LiFePO₄ battery fuse check for that.
Starter motor (cranking) cables follow different rules. Bundled cables, conduit and higher temperatures carry less current than the table assumes.