Load

Attwood Turbo 4000 Series II 1749-4 wiring diagram

See the Attwood Turbo 4000 Series II 1749-4 connection points and wiring example. Open the diagram in Crimp to add your equipment and plan the cables between them.

Open this example as a new project. Use your own parts and cable lengths to make the plan yours.

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

12 V system

Wire
1.5 mm² · 16 AWG
Example fuse
5 A
Design current
2.9 A
Voltage drop
1.7%

Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

The 1749-4 example uses Attwood's 5 A fuse and 2.9 A running figure at 13.6 V. The positive feed also needs the helm switch. Verify duct routing, dryness, flow direction, actual cable routing and the engine-compartment voltage-drop allowance. Manufacturer installation manual

Show sizes in AWG

Wiring diagram

How the Turbo 4000 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Attwood Turbo 4000 Series II 1749-4 wiring diagram, 1.5 mm² (16 AWG) positive feed protected by a 5 A fuse and a matching negative return between the 12 V battery bank and the unit.

The 1749-4 example uses Attwood's 5 A fuse and 2.9 A running figure at 13.6 V. The positive feed also needs the helm switch. Verify duct routing, dryness, flow direction, actual cable routing and the engine-compartment voltage-drop allowance. Manufacturer installation manual

Edit this wiring example

Installation notes

Connections and installation requirements.

Guidance for this model, with sources linked beside the relevant advice.

Verified against the manufacturer's documentation (rev. 69465 Rev A, 09/01; current Attwood catalog pp. 36–38), checked 2026-10-01. Manufacturer documentation →

A ventilation blower, not a bilge pump

1749-4 is the retail 12 V water-resistant Turbo 4000 Series II blower for 4-inch ventilation hose. Its role is to move air from the engine/bilge space to an exterior vent. Water resistance does not authorize submersion or mounting where bilge water is drawn through it.

The manufacturer gives 230 CFM open flow and 125 CFM in a specified test system with duct, a bend, collector and vent. Use the installed ventilation path when assessing airflow; the free-air number alone does not establish adequate ventilation for an engine compartment.

Wire for the blower's actual running load

Connect yellow positive through the helm on/off switch and specified 5 A fuse, with black negative return. The reviewed instruction table gives 2.9 A at 13.6 V. The catalog uses that operating point; it does not borrow the 24 V blower's current or treat the fuse as consumption. No measured starting surge was recovered.

Size extensions for the actual circuit length, ampacity and voltage drop, and keep connections protected from moisture. The older instruction sheet shows a maximum source-to-fuse distance; use the protection placement required for the actual installation rather than assuming that old drawing makes every long unprotected battery lead acceptable. The catalog terminal limit is a protection-based planning bound.

Mount the air path to stay dry

Mount high above the bilge on a suitable surface, clear of spray and deck wash, with the flow arrow pointing toward the exhaust vent. Follow the recommended angled orientation so moisture does not collect in the housing. Secure the hose over the retention features without crushing the plastic.

Route the intake pickup toward the low part of the space being ventilated while keeping it above possible bilge-water submersion. Run the discharge to the exterior vent with few bends and no collapsed hose. An apparently healthy spinning fan can move very little useful air through a blocked or badly routed duct.

Use and inspect before starting an engine

Attwood directs operation for at least four minutes before engine start, followed by checking the compartment for fuel-vapor odor, and operation below cruising speed. The sheet also says not to operate while refueling or above its 71 °C ambient limit. Keep the blower reminder label at the helm.

Commission by checking the direction and useful flow at the exterior discharge, not only the sound of the motor. If flow is poor, inspect duct restrictions, pickup obstruction and rotation/airflow orientation. If it is silent, check voltage at the blower, switch and fuse. Isolate power before servicing; if fuel vapor remains, resolve its source before engine starting.

Build it out

Connect it to the rest of your system.

Add 1749-4 to your diagram, then connect your batteries, chargers and loads. Crimp calculates cable sizes and checks the connections as you draw.

Every cable you draw there is sized against ABYC E-11, from the same tables as the reference on this page.

Technical reference

Specifications, terminals and supporting parts.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Nominal voltage
12 V
Compatible systems
12 V
Continuous draw
2.9 A

Supporting parts

  1. 6.1 m total of 1.5 mm² (16 AWG) marine cable
  2. Terminations for 1.5 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 5 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

+

pos

positive · input

5 A

−

neg

negative · input

5 A

Method & provenance

Where the specifications and sizing come from.

Manufacturer specifications describe the equipment. Crimp calculates cable results from the circuit and assumptions you enter.

From the maker

What the catalog says

Manufacturer, model, ratings and which terminal does what come from the catalog. A newer revision, or the nameplate on the unit in your hand, can say something different — when it does, the nameplate wins.

ABYC E-11

What Crimp worked out

Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. The run length and the current above are what drive the result. Crimp doesn't know how warm your space gets; draw the cable inside an engine-bay zone on the canvas and it sizes for the heat.

Read how the sizing works

Next step

Plan your installation with Turbo 4000.

Open this example as a new project. Add your equipment and cable lengths, then review the sizing and checks for your setup.