Charger

Victron Blue Smart IP67 12/25 wiring diagram

Blue Smart IP67 12/25: 25A charger for 12V batteries, with 10A Low mode and M8 ring leads. Protective earth is required. Separate 230V (180–265 VAC) and 120V (100–130 VAC) versions; mount protected and ventilated.

Compatible systems
12 V
Rated output
25 A

Wiring diagram

How the BS IP67 25 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Victron Blue Smart IP67 12/25 wiring example with 3 components: BS IP67 25, Battery disconnect, House bank. 3 cable connections. Crossings are not junctions.BS IP67 25 BATT + to Battery disconnect A: 10 mm² · 35 A fuse, 3 m one way. BS IP67 25 BATT − to House bank −: 10 mm², 3 m one way. Battery disconnect B to House bank +: 10 mm² · 35 A fuse, 30 cm one wayBS IP67 25 BATT + to Battery disconnect A: 10 mm² · 35 A fuse, 3 m one wayBS IP67 25 BATT − to House bank −: 10 mm², 3 m one wayBattery disconnect B to House bank +: 10 mm² · 35 A fuse, 30 cm one wayVictron Blue Smart IP67 12/25BS IP67 25BATT +BATT +BATT −BATT −Main Battery SwitchBattery disconnectAB12 V 100 Ah AGM placeholder bank. Example bank only: select the correct charger profile and confirm the actual battery's capacity, charging-current acceptance, voltage and temperature limits. Placeholder current limits are not manufacturer battery specifications.House bank++−−10 mm² · 35 A fuse10 mm²10 mm² · 35 A fuse
Victron Blue Smart IP67 12/25 wiring example with 3 components: BS IP67 25, Battery disconnect, House bank. 3 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Cable labels are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

12 V system

Wire
10 mm² · 8 AWG
Example fuse
35 A
Design current
25 A
Voltage drop
2.2%

Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Show sizes in AWG

Supporting parts

  1. 6.1 m total of 10 mm² (8 AWG) marine cable
  2. Terminations for 10 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 35 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. Rev 06 — 09/2026), checked 2026-10-01. Manufacturer documentation →

Which 12/25 charger is this?

The Blue Smart IP67 12/25 is a mains charger for a nominal 12 V battery, with 25 A maximum charge current and 10 A Low mode. It is not an inverter or a DC-DC converter. Confirm the AC nameplate: the reviewed 230 V version accepts 180–265 VAC; the separate 120 V manual specifies 100–130 VAC. These are separate products, not one universal-input unit.

How do the connections map?

BATT + / BATT − represent the permanently attached red/black cable with M8 ring terminals. This model is supplied with 6 mm² cable. The manual permits shortening and reterminating the DC lead; an extension needs a separate conductor, voltage-drop, and protection check.

AC L / AC N / AC ⏚ represent the mains cord, including its protective-earth conductor. Preserve that earth connection through the genuine supply cord and an earthed outlet; the revised symbol includes it. Connect DC with sources and loads isolated, verify polarity, then apply AC. For temporary charging in a vehicle, follow the manual's chassis-connection sequence.

Which protection is required?

The external-protection table, printed page 16 gives 40–50 A for this model, selected with the actual conductor and fuse type. Place that protection close to battery positive. The 12/25 has no fuse in its supplied DC cable; its internal fuse does not protect the battery-side cable. The specification table also lists a 30 A internal fuse, which is not user-serviceable.

What must be configured?

Use VictronConnect to choose chemistry and current. Normal mode uses 14.4 / 13.8 / 13.2 V for absorption, float, and storage. The lithium preset uses 14.2 V absorption and disables lead-acid temperature compensation. Those presets require the battery manufacturer's approval; they do not bypass a BMS or permit charging lithium below 0°C. Select Low mode if the bank cannot accept 25 A. House loads consume part of the charger output, reducing current available to recharge the battery.

Where should it be mounted?

Mount vertically with both cables downward, on a nonflammable surface, with 100 mm clearance above and below. Despite the IP67 enclosure, the installation chapter calls for a protected, ventilated location away from flammable gases and liquids, never directly above or sealed in with the battery. Rated output is available up to 40°C, then derates. Waterproofing does not remove the need to protect plugs and cable joints.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Blue Smart IP67 12/25: 25A charger for 12V batteries, with 10A Low mode and M8 ring leads. Protective earth is required. Separate 230V (180–265 VAC) and 120V (100–130 VAC) versions; mount protected and ventilated.

Compatible systems
12 V
Rated output
25 A
Planning charge current
24 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

AC L

neutral · input

8 A

AC N

neutral · input

8 A

AC ⏚

ground · bidi

8 A

BATT +

positive · output

25 A

BATT −

negative · output

25 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with BS IP67 25.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Free for up to 10 equipment components, with no account needed. Cables, busbars and fuse hardware do not count toward the limit. Your drawing saves in this browser. File exports are included with Crimp Pro.