Model AC180

1,800 W / 1,152 Wh LiFePO4 portable power station. The regulated 12 V cigarette-socket output supplies up to 10 A (about 120 W); AC output is 1,800 W continuous with a 2,700 W surge.

Open in Crimp →
Reference image unavailable
Bluetti AC180 Power Station · 2 terminals
01 — Reference run

A sizing result with its assumptions attached.

Conductor4 mm²11 AWG
Fuse15 Apositive run
Voltage drop2.2%3 m one way
Design current10 A12 V system

Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. The design current is the unit's rated output. The Crimp engine applies its ordinary continuous-load headroom, voltage-drop budget, terminal clamp, and standard fuse ladder. The 3 m one-way run is a stated reference, not a universal installation prescription.

02 — Catalog specification

The part the engine actually sees.

Nominal voltage
12 V
Capacity
90 Ah
Rated output
10 A

Terminal map

TerminalPolarityDirectionRating
12V +positiveoutput10 A
12V −negativeoutput10 A
03 — Supporting parts

What belongs around it.

  • 6 m total of 4 mm² (11 AWG) marine cable
  • Four 4 mm² cable lugs matched to the equipment studs
  • 15 A fuse and holder on the positive run
  • Heat-shrink, strain relief, and terminal boots sized to the cable

See what it changes in your system

With JavaScript enabled, describe your existing boat, van, or off-grid system here. The model supplies topology; Crimp's engine computes the attachment, resized runs, checks, and supporting basket.

04 — Method & provenance

What is known, assumed, and computed.

Catalog profile

The manufacturer, model, ratings and terminal map are maintained as planning data in Crimp's component catalog. Confirm the current manufacturer manual, exact revision and installed nameplate before ordering or wiring.

Engine reference

Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. The published conductor, fuse and voltage-drop result uses the visible reference length and current basis; it is not a universal installation prescription.

Read the complete methodology →