Charge a 24 V house bank from a 12 V vehicle. Follow the Orion XS 1400’s two protected positive feeds, shared ground and remote link, then set both current limits for your alternator.
Free, no account needed.
- Part number
- ORI242417040
- Input voltage
- 9–35 V
- Output voltage
- 10–35 V adjustable
Checked against the manufacturer manual, Nov 2026.
Wiring diagram
A 12 V vehicle charging a 24 V house bank
Protect both battery-positive cables and join both returns at GND. The factory H–L link is shown; configure input voltage, charging profile and engine detection in VictronConnect. The upstream alternator is omitted; add it to simulate automatic charging.

Rev 03 specifies 60–70 A battery fuses and 16 mm² cable for runs below 5 m. This example selects 60 A at each battery. The 12-to-24 V charge estimate is constrained by the 50 A input limit; configure both limits and the battery profile in VictronConnect. Manufacturer installation manual
Get wire sizes for my setupFree, no account needed.
Quick answers
Cable and fuse
16 mm² (6 AWG) with a 60 A fuse for a 80 cm one-way run (24 V system). Sizes for other lengths
House-bank output cable reference
The 50 A input limit also limits output power. A 12 V source cannot deliver the full 1400 W rating shown for higher-voltage operation.
80 cm one way
24 V system
- Wire
- 16 mm² · 6 AWG
- Example fuse
- 60 A
- Design current
- 50 A
- Voltage drop
- 0.4%
Cable size by run length
| One way | Wire | Fuse | Voltage drop |
|---|---|---|---|
| 80 cm (worked example above) | 16 mm² · 6 AWG | 60 A | 0.4% |
| 1 m | 16 mm² · 6 AWG | 60 A | 0.5% |
| 2 m | 16 mm² · 6 AWG | 60 A | 1.0% |
| 3 m | 16 mm² · 6 AWG | 60 A | 1.4% |
| 5 m | 16 mm² · 6 AWG | 60 A | 2.4% |
Same circuit and current, sized by Crimp's engine at each length. Longer runs, warmer spaces or engine rooms need the editor's full check.
Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.
Already have a cable size? Check a simple copper run at your current and length with the DC voltage drop calculator in mm² or AWG.
Run-length and manufacturer assumptions
The editable example uses 10 ft (3 m) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.
Rev 03 specifies 60–70 A battery fuses and 16 mm² cable for runs below 5 m. This example selects 60 A at each battery. The 12-to-24 V charge estimate is constrained by the 50 A input limit; configure both limits and the battery profile in VictronConnect. Manufacturer installation manual
Supporting parts
- 7.6 m total of 16 mm² (6 AWG) marine cable
- 5 cm total of 1.5 mm² (16 AWG) marine cable
- Terminations for 16 mm² and 1.5 mm² cable, matched to the equipment's screw terminals, leads or studs
- 60 A fuse and holder on the positive run
- Heat-shrink, strain relief and terminal boots sized to the cable
Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.
Installation notes
Before you install.
Open a question for model-specific guidance and sources.
Verified against the manufacturer's documentation (rev. Rev 03 — 09/2026), checked 2026-11-26. Manufacturer documentation →
Which Victron Orion XS 1400 is this?
This is the non-isolated ORI242417040, with configurable 12 V or 24 V charging and separate 50 A input and output limits. Its input range is 9–35 V and output range 10–35 V. It differs from the Orion XS 12/12-50 A: this example steps a 12 V vehicle supply up to a 24 V house bank.
How is the Victron Orion XS 1400 wired?
IN + connects to the protected vehicle positive, OUT + to the protected house-battery positive, and both returns join the single GND terminal. The factory REMOTE H–REMOTE L link enables operation. VE.Direct and external BMS controls are outside this example.
The Rev 03 installation table recommends 60–70 A fuses and 16 mm² cable for runs below 5 m. The Technical reference covers the example’s output circuit.
What should I bear in mind with the Victron Orion XS 1400?
The input-current limit matters as much as the output setting.
- 12-to-24 V charging: a 12 V source at the 50 A input ceiling cannot supply the full advertised 1400 W. Available input power limits output current; see the technical data.
- Configuration: check input voltage, battery profile, both current limits and engine detection in VictronConnect. The remote link alone does not prove the engine is running. Follow the operation manual.
What do owners and installers say about the Victron Orion XS 1400?
Configuration can explain a low-input-voltage warning even when the wiring worked with another charger. In a 12-to-24 V installation thread, a responder identified a 24 V input setting on a 12 V vehicle. The owner subsequently confirmed charging worked. Check settings before assuming the charger has failed.
What belongs around the Victron Orion XS 1400?
Adapt the two-bank example above and compare the Orion XS 12/12-50 A for a 12 V house bank. Explore dual-battery systems and use the wire-size calculator when changing cable lengths.
Technical reference
Specifications and terminal map.
Check the model, ratings and connection points against your own unit before choosing installation hardware.
Catalog specification
Orion XS 1400 (ORI242417040), non-isolated 12/24 V DC-DC charger with independent 50 A input and output limits. The 12-to-24 V example is constrained by input power; 1400 W is not available from a 12 V input.
- Part number
- ORI242417040
- Input voltage
- 9–35 V
- Output voltage
- 10–35 V adjustable
- Input / output limits
- 50 A each, independently adjustable
- Rated power
- 1400 W at higher operating voltage
- Ground
- Common, non-isolated
Terminal map
IN + and OUT + are separate positive paths. GND is one common negative terminal. REMOTE H and REMOTE L carry the factory enable link shown here. VE.Direct, external BMS control and emergency reverse charging are outside this example.
IN +
positive · input
OUT +
positive · output
GND
negative · bidi
REMOTE L
signal · input
REMOTE H
signal · input
A dash means a current rating is not specified here.
Sources and sizing method
Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.
Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.