Battery wiring guide
How to wire batteries in series and in parallel
Wiring batteries in series joins one battery's negative to the next one's positive: the voltages add and the capacity stays the same, so two 12 V 100 Ah batteries make 24 V 100 Ah. Wiring them in parallel joins positive to positive and negative to negative: the voltage stays the same and the capacities add, so the same two make 12 V 200 Ah. Both store the same energy, about 2,560 Wh for two 12.8 V 100 Ah lithium batteries. Use identical batteries of the same age, charge each one full before joining them, and fuse the bank's positive at the battery.
Two batteries in parallel: 12 V, 200 Ah
Positive to positive, negative to negative, with links of equal length and size. The bank's positive leaves from battery 1 and its negative from battery 2, so both batteries work equally hard.
4 components · 6 conductors

Live Crimp simulation. Try equipment states and battery charge. Connections and cable sizes are listed below.
View full screenRed = positive · dark = return. Crossings are not junctions. Read the assumptions before adapting a circuit.
Two batteries in series: 24 V, 100 Ah
One link, from battery 1's negative to battery 2's positive. The free positive and free negative are the 24 V bank terminals.
4 components · 5 conductors

Live Crimp simulation. Try equipment states and battery charge. Connections and cable sizes are listed below.
View full screenRed = positive · dark = return. Crossings are not junctions. Read the assumptions before adapting a circuit.
Four batteries in series-parallel: 24 V, 200 Ah
Two series strings of two, then the strings joined in parallel at their ends, with the bank taken off diagonally.
6 components · 8 conductors

Live Crimp simulation. Try equipment states and battery charge. Connections and cable sizes are listed below.
View full screenRed = positive · dark = return. Crossings are not junctions. Read the assumptions before adapting a circuit.
Series, parallel and series-parallel compared
With Renogy 12.8 V 100 Ah LiFePO4 batteries, as in the drawings. Energy is voltage × capacity.
| Voltage and capacity | Energy | |
|---|---|---|
| One battery | 12.8 V, 100 Ah | 1,280 Wh |
| Two in parallel | 12.8 V, 200 Ah | 2,560 Wh |
| Two in series | 25.6 V, 100 Ah | 2,560 Wh |
| Four in series-parallel (2S2P) | 25.6 V, 200 Ah | 5,120 Wh |
Series halves the current for the same power, which is why 24 V systems use thinner cable. Parallel keeps the system at 12 V, so it works with 12 V chargers and loads as they are.
Step by step
01
Match the batteries
Use the same brand, model and capacity, bought at about the same time. Renogy asks for batteries bought within about a month of each other and warns against joining ones more than six months apart.
02
Charge each battery full first
Charge every battery on its own until full, and check they are within 0.1 V of each other before you join them. Renogy then suggests leaving them in parallel for 12 to 24 hours.
03
Make the links
In parallel, join positives together and negatives together with cables of the same length and size. In series, join each battery's negative to the next one's positive. For series-parallel, build the series strings first, then join their ends.
04
Take the bank off diagonally
Take the main positive from one end of the bank and the main negative from the other end. Victron's Wiring Unlimited shows this, or bus bars with equal cables, so the current path through every battery is the same length.
05
Fuse the bank positive
Fit the main fuse on the bank's positive terminal, before anything else connects. In the drawings that is a 100 A terminal fuse protecting 16 mm² cable.
06
Check the voltage
Measure across the bank terminals: about 13 V for a 12 V lithium bank in parallel, about 26 V for two in series.
Cable and fuse sizes
Sized by Crimp's ABYC E-11 based engine for the lengths shown. Lengths are one way; AWG is the approximate counterpart of the metric size.
Two batteries in parallel: 12 V, 200 Ah
| Connection | Length | Wire | Design current | Fuse | Drop |
|---|---|---|---|---|---|
| C1 · Battery 1 · 12 V 100 Ah + → Battery 2 · 12 V 100 Ah + | 30 cm1.0 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C2 · Battery 1 · 12 V 100 Ah − → Battery 2 · 12 V 100 Ah − | 30 cm1.0 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C3 · Battery 1 · 12 V 100 Ah + → Fuse block IN + | 1 m3.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.04% |
| C4 · Battery 2 · 12 V 100 Ah − → Fuse block IN − | 1 m3.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.04% |
| C5 · Fuse block 1 + → Compressor fridge (12/24 V) + | 3 m9.8 ft | 1.5 mm²AWG 16 | 5 A | 15 A | 1.37% |
| C6 · Compressor fridge (12/24 V) − → Fuse block 1 − | 3 m9.8 ft | 1.5 mm²AWG 16 | 5 A | — | 1.37% |
Two batteries in series: 24 V, 100 Ah
| Connection | Length | Wire | Design current | Fuse | Drop |
|---|---|---|---|---|---|
| C1 · Battery 1 · 12 V 100 Ah (bank +) − → Battery 2 · 12 V 100 Ah (bank −) + | 30 cm1.0 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C2 · Battery 1 · 12 V 100 Ah (bank +) + → Fuse block IN + | 1 m3.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.02% |
| C3 · Battery 2 · 12 V 100 Ah (bank −) − → Fuse block IN − | 1 m3.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.02% |
| C4 · Fuse block 1 + → Compressor fridge (12/24 V) + | 3 m9.8 ft | 1.5 mm²AWG 16 | 5 A | 7.5 A | 0.68% |
| C5 · Compressor fridge (12/24 V) − → Fuse block 1 − | 3 m9.8 ft | 1.5 mm²AWG 16 | 5 A | — | 0.68% |
Four batteries in series-parallel: 24 V, 200 Ah
| Connection | Length | Wire | Design current | Fuse | Drop |
|---|---|---|---|---|---|
| C1 · String A · battery 1 (+) − → String A · battery 2 + | 30 cm1.0 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C2 · String B · battery 3 − → String B · battery 4 (−) + | 30 cm1.0 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C3 · String A · battery 1 (+) + → String B · battery 3 + | 40 cm1.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C4 · String A · battery 2 − → String B · battery 4 (−) − | 40 cm1.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.01% |
| C5 · String A · battery 1 (+) + → Fuse block IN + | 1 m3.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.02% |
| C6 · String B · battery 4 (−) − → Fuse block IN − | 1 m3.3 ft | 16 mm²AWG 6set size | 5 A | — | 0.02% |
| C7 · Fuse block 1 + → Compressor fridge (12/24 V) + | 3 m9.8 ft | 1.5 mm²AWG 16 | 5 A | 7.5 A | 0.68% |
| C8 · Compressor fridge (12/24 V) − → Fuse block 1 − | 3 m9.8 ft | 1.5 mm²AWG 16 | 5 A | — | 0.68% |
A dash means the cable has no fuse of its own: a negative, a cable past a switch, or a run protected by the fuse upstream of it. Fuses on a battery post or in an inline holder are drawn on the diagram.
Common mistakes
Crimp's checks on these drawings: 0 critical, 11 to review. They stay visible when you open it.
- Taking both main cables from the same battery in a parallel bank. That battery does most of the work and wears out first.
- Mixing old and new, or different capacities. The weaker battery limits the bank and is worked hardest.
- Joining batteries at different charge levels. A large voltage difference drives a large current between them the moment they connect.
- Running 12 V loads off one battery of a 24 V series bank. It unbalances the bank; use a 24/12 converter instead.
- Exceeding the maker's series or parallel limit. Renogy's Core Mini allows up to four in series.
- warning: Check current sharing (Two batteries in parallel: 12 V, 200 Ah)
- warning: CRX-50: verify manufacturer wiring (Two batteries in parallel: 12 V, 200 Ah)
- warning: No charging source (Two batteries in parallel: 12 V, 200 Ah)
- info: Check fuse suitability: Battery 1 · 12 V 100 Ah (+1) (Two batteries in parallel: 12 V, 200 Ah)
- warning: CRX-50: verify manufacturer wiring (Two batteries in series: 24 V, 100 Ah)
- warning: No charging source (Two batteries in series: 24 V, 100 Ah)
- info: Check fuse suitability: Battery 1 · 12 V 100 Ah (bank +) (+1) (Two batteries in series: 24 V, 100 Ah)
- warning: Check current sharing (Four batteries in series-parallel: 24 V, 200 Ah)
- warning: CRX-50: verify manufacturer wiring (Four batteries in series-parallel: 24 V, 200 Ah)
- warning: No charging source (Four batteries in series-parallel: 24 V, 200 Ah)
- info: Check fuse suitability: String A · battery 1 (+) (+3) (Four batteries in series-parallel: 24 V, 200 Ah)
A planning example, not an installation certificate. Sizing follows Crimp's published method; check the manufacturer documents below for your exact parts.
Questions
What happens when you wire batteries in series?
The voltages add and the capacity stays the same. Two 12.8 V 100 Ah batteries in series make a 25.6 V, 100 Ah bank. The same current flows through every battery, so they must be matched: a weaker one runs flat first and limits the bank.
What happens when you wire batteries in parallel?
The voltage stays the same and the capacities add. Two 12.8 V 100 Ah batteries in parallel make a 12.8 V, 200 Ah bank. The current splits between them, which is why equal cable lengths and a diagonal take-off matter.
Is series or parallel better?
Neither holds more energy: both arrangements of two 100 Ah batteries store about 2,560 Wh. Parallel keeps 12 V, so existing 12 V chargers and loads work unchanged. Series gives 24 V, which halves the current for the same power and allows thinner cables, but every charger and load must suit 24 V.
Can I wire lithium batteries in series?
Only if the maker allows it, and up to their limit. Renogy's Core Mini allows up to four in series. Each battery's BMS protects only that battery, so charge them to the same voltage first and check them separately now and then.
Do I need a fuse on each battery in a parallel bank?
These drawings use one main fuse on the bank positive. Some makers and larger banks call for a fuse on every battery, so that a fault in one battery is not fed by the others; check your battery's manual.
What size cable should join the batteries?
Size the links like the main cable, because in a fault they carry the bank's full current. In these drawings every bank cable is 16 mm², matching what the 100 A main fuse protects.
Sources
Reviewed 26 November 2026.
Draw your own circuit, with every wire and fuse sized.
Start from this diagram