Battery shunt wiring diagram: how to wire a SmartShunt or battery monitor
A battery shunt measures every amp that goes into and out of the battery, so it has to sit in the only path the negative current can take. Connect the battery negative, and nothing else, to the shunt's BATTERY MINUS side. Connect the negative bus bar, where every load and charger returns, to its SYSTEM MINUS side (LOAD MINUS on older units). Then run the small red Vbatt+ lead, with the fuse Victron supplies in it, from battery positive to power the shunt. Anything wired straight to the battery negative bypasses the shunt and its current is never counted, which is the usual reason a battery monitor's state of charge drifts.
The wiring diagram
The solar controller's negative and the fuse block's negative both land on the bus behind the shunt, so charge and load current are both counted. Only the shunt touches the battery negative.
8 components · 12 conductors

Live Crimp simulation. Try equipment states and battery charge. Connections and cable sizes are listed below.
View full screenRed = positive · dark = return. Crossings are not junctions. Read the assumptions before adapting a circuit.
SmartShunt connections
The connections on a Victron SmartShunt 500 A, from Victron's installation guide.
| Connection | What it is | Connect it to |
|---|---|---|
| BATTERY MINUS | Battery side of the shunt, M10 bolt | The house battery negative, and nothing else |
| SYSTEM MINUS | System side, M10 bolt (LOAD MINUS on older units) | The negative bus bar carrying every load and charger return |
| Vbatt+ | Power for the shunt's electronics | Battery positive, through the supplied red lead and its 1 A slow-blow fuse |
| Aux | One configurable sense input | A starter battery, a midpoint or a temperature sensor, or nothing |
| VE.Direct | Data port | A GX device or interface, or nothing |
Victron gives a maximum torque of 21 N·m for the 500 A model's M10 bolts.
Step by step
01
Put the shunt next to the battery
Mount it in a dry place, close to the battery negative, so the cable between them is short. The IP21 SmartShunt is for dry locations; there is a separate IP65 version.
02
Battery negative to BATTERY MINUS
Run the battery's main negative cable to the BATTERY MINUS bolt. Move every other wire off the battery negative terminal.
03
SYSTEM MINUS to the negative bus
Connect SYSTEM MINUS to the negative bus bar with cable as heavy as the battery's main negative. Every return, from the fuse block, the solar controller, the inverter or the charger, lands on that bus.
04
Fit the Vbatt+ lead
Connect the supplied red lead, with its 1 A slow-blow fuse, from the shunt's Vbatt+ to battery positive. It only powers the shunt; it does not protect the main cables.
05
Leave Aux and VE.Direct for later
Aux takes one function at a time: a second battery's voltage, a midpoint or a temperature sensor. VE.Direct connects a GX device. Neither is needed to measure the battery.
06
Set it up before trusting it
In VictronConnect, set the battery capacity, charged voltage and synchronisation. The factory defaults suit lead-acid; a lithium battery needs its own settings.
Cable and fuse sizes
Sized by Crimp's ABYC E-11 based engine for the lengths shown. Lengths are one way; AWG is the approximate counterpart of the metric size.
| Connection | Length | Wire | Design current | Fuse | Drop |
|---|---|---|---|---|---|
| C1 · House battery + → Positive bus bar + | 50 cm1.6 ft | 6 mm²AWG 10 | 15 A | — | 0.17% |
| C2 · House battery − → SmartShunt 500 A BATT − | 30 cm1.0 ft | 6 mm²AWG 10 | 15 A | — | 0.10% |
| C3 · House battery + → SmartShunt 500 A Vbatt+ power | 50 cm1.6 ft | 0.75 mm²AWG 18set size | Switched circuit | 1 A | 0.00% |
| C4 · SmartShunt 500 A LOAD − → Negative bus bar − | 30 cm1.0 ft | 6 mm²AWG 10 | 15 A | — | 0.10% |
| C5 · Positive bus bar 1 + → Fuse block IN + | 50 cm1.6 ft | 6 mm²AWG 10 | 5 A | — | 0.06% |
| C6 · Fuse block IN − → Negative bus bar 1 − | 50 cm1.6 ft | 6 mm²AWG 10 | 5 A | — | 0.06% |
| C7 · Fuse block 1 + → Compressor fridge + | 3 m9.8 ft | 6 mm²AWG 10 | 5 A | 15 A | 0.34% |
| C8 · Compressor fridge − → Fuse block 1 − | 3 m9.8 ft | 6 mm²AWG 10 | 5 A | — | 0.34% |
| C9 · Solar panel 100 W + → Solar charge controller PV + | 4 m13.1 ft | 1.5 mm²AWG 16 | 5.4 A | — | 1.35% |
| C10 · Solar panel 100 W − → Solar charge controller PV − | 4 m13.1 ft | 1.5 mm²AWG 16 | 5.4 A | — | 1.35% |
| C11 · Solar charge controller BATT + → Positive bus bar 2 + | 1 m3.3 ft | 2.5 mm²AWG 13set size | 15 A | 20 A | 0.82% |
| C12 · Solar charge controller BATT − → Negative bus bar 2 − | 1 m3.3 ft | 2.5 mm²AWG 13 | 15 A | — | 0.82% |
A dash means the cable has no fuse of its own: a negative, a cable past a switch, or a run protected by the fuse upstream of it. Fuses on a battery post or in an inline holder are drawn on the diagram.
Common mistakes
Crimp's checks on this drawing: 0 critical, 2 to review. They stay visible when you open it.
- Leaving a charger or load on the battery negative. Its current bypasses the shunt and the state of charge drifts.
- Wiring the shunt backwards. Charge and discharge swap sign: the monitor shows charging when it should show discharging.
- Choosing the shunt rating as the fuse size. 500 A is how much the shunt can measure, not what the battery cables or fuse should be.
- Skipping the setup. With the default capacity and charged voltage the percentage is guesswork.
- Expecting the shunt to cut off loads. Its alarms are notifications; it has no relay to disconnect anything.
- warning: Solar panels can’t be switched off
- info: Check fuse suitability: House battery
A planning example, not an installation certificate. Sizing follows Crimp's published method; check the manufacturer documents below for your exact parts.
Questions
Where does a battery shunt go?
In the battery negative, between the battery and everything else. The battery negative goes to one side (BATTERY MINUS) and the negative bus with every return goes to the other (SYSTEM MINUS).
Does a shunt go on the positive or negative?
The SmartShunt and most battery monitor shunts go in the negative. They still need a small positive connection, the fused Vbatt+ lead, to power their electronics.
What fuse does the SmartShunt Vbatt+ lead need?
Victron supplies the red Vbatt+ lead with a 1 A slow-blow fuse fitted. Use that lead; the fuse protects the small wire, not the battery cables.
Why is my battery monitor percentage wrong?
Check for a bypass first: any return that lands on the battery negative is not measured. Then check the battery capacity, the charged voltage and synchronisation in VictronConnect, and whether the shunt is wired the right way round.
What size cable for a battery shunt?
The same size as the battery's main negative, because all the current flows through it. In the drawing that is 6 mm² for a small system; a big inverter needs much heavier cable.
Can a SmartShunt turn off loads when the battery is low?
Not by itself. Its alarms show in VictronConnect or on a GX device, and the SmartShunt has no relay. Switching loads off needs separate hardware.