Teltonika RUTX11 Standard wiring diagram

Standard RUTX11 accepts 9–50 V DC and has 16 W maximum consumption. The 12 V current estimate is 16 W / 12 V. This symbol models its DC power connector; passive PoE is an alternative input and is not IEEE 802.3af/at/bt compatible. Excludes the narrower-voltage railway variant.

Nominal voltage
12 V
Compatible systems
12 V / 24 V / 48 V
Rated power
16 W

Wiring diagram

How the RUTX11 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Teltonika RUTX11 Standard wiring example with 3 components: House bank, Fused DC distribution, RUTX11. 4 cable connections. Crossings are not junctions.Fused DC distribution 1 to RUTX11 +: 1.5 mm² · 2 A fuse, 3 m one way. Fused DC distribution 1 to RUTX11 −: 1.5 mm², 3 m one way. House bank + to Fused DC distribution IN +: 1.5 mm² · 2 A fuse, 30 cm one way. House bank − to Fused DC distribution IN −: 1.5 mm², 30 cm one wayFused DC distribution 1 to RUTX11 +: 1.5 mm² · 2 A fuse, 3 m one wayFused DC distribution 1 to RUTX11 −: 1.5 mm², 3 m one wayHouse bank + to Fused DC distribution IN +: 1.5 mm² · 2 A fuse, 30 cm one wayHouse bank − to Fused DC distribution IN −: 1.5 mm², 30 cm one way12 V 200 Ah house bankHouse bank++−−Blue Sea 5025 ST Blade Fuse BlockFused DC distributionIN +IN +IN −IN −1111Teltonika RUTX11 StandardRUTX11++−−1.5 mm² · 2 A fuse1.5 mm²1.5 mm² · 2 A fuse1.5 mm²
Teltonika RUTX11 Standard wiring example with 3 components: House bank, Fused DC distribution, RUTX11. 4 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Cable labels are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

12 V system

Wire
1.5 mm² · 16 AWG
Example fuse
2 A
Design current
1.3 A
Voltage drop
0.8%

Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Show sizes in AWG

Supporting parts

  1. 6.1 m total of 1.5 mm² (16 AWG) marine cable
  2. Terminations for 1.5 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 2 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. RUTX11 datasheet v12, ©2025; official quick start and power documentation), checked 2026-10-01. Manufacturer documentation →

Which RUTX11 variant is covered?

This is the standard RUTX11, a mobile router with LTE, Wi-Fi and Ethernet. The manufacturer datasheet, power section, page 11, specifies 9–50 V DC and 16 W maximum consumption. It separately limits railway order code RUTX11 020G00 to 24–36 V; that variant is outside this entry. At nominal 12 V, 16 W corresponds to approximately 1.33 A. This maximum budget is not an idle-current measurement.

Which connection is the power input?

The official powering guide identifies the 4-pin DC connector and its supply/ground contacts. The remaining connector positions are digital I/O, not additional power terminals. This catalog exposes only the positive and return of the DC input. Check the device's connector diagram rather than relying on the connector's physical orientation or another router's cable colors.

LAN1 also supports passive PoE, Mode B, 9–50 V, but it is not IEEE 802.3af, 802.3at or 802.3bt PoE. That is an alternative power arrangement, not an output modeled by the two catalog terminals. Do not assume an ordinary active-PoE switch will power it. The reviewed sources do not prescribe an external DC branch-fuse rating; protect the installation's feed for its wiring and applicable supply requirements.

How should mounting and initial setup be handled?

Install in a dry location with room for airflow and antenna cables; the datasheet rates the enclosure IP30, not watertight. Fit the correct mobile and Wi-Fi antennas, insert the SIM according to the official quick-start guide, and follow its first-login and password setup before relying on connectivity. Keep radio/antenna installation within the manufacturer's guidance for the intended region.

What should be checked if connection or power is unreliable?

Measure supply at the router under load, then check the DC plug, polarity and upstream protection. For network failures, distinguish mobile registration, SIM/PIN or APN problems from loss of power; use the router's status information rather than repeated factory resets. The terminal boundary of 16 W / 9 V, about 1.78 A, is a calculated input-current planning envelope across the specified voltage range, not a separately published connector rating. Energy estimates use 12 V nominal and should be replaced with measurements for the actual radio traffic and accessories.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Standard RUTX11 accepts 9–50 V DC and has 16 W maximum consumption. The 12 V current estimate is 16 W / 12 V. This symbol models its DC power connector; passive PoE is an alternative input and is not IEEE 802.3af/at/bt compatible. Excludes the narrower-voltage railway variant.

Nominal voltage
12 V
Compatible systems
12 V / 24 V / 48 V
Rated power
16 W
Continuous draw
1.3 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

+

positive · input

1.7777777777777777 A

−

negative · input

1.7777777777777777 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with RUTX11.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Free for up to 10 equipment components, with no account needed. Cables, busbars and fuse hardware do not count toward the limit. Your drawing saves in this browser. File exports are included with Crimp Pro.