A rocker switch goes in the positive wire of the thing it controls, after that circuit's fuse. Run a wire from a fuse block slot to the switch's supply terminal, a second wire from the switch's output terminal to the load's positive, and return the load's negative to the negative bus. The switch never touches the negative wire. A lighted switch adds one or two lamp terminals: the lamp's negative goes to ground, so the switch can light up. Size the fuse to the wire, and use a relay when the load draws more than the switch is rated for.
The wiring diagram
Each load has its own fuse and its own switch. The switches sit in the positive wires; the negatives go straight back to the fuse block.
6 components · 8 conductors

Live Crimp simulation. Try equipment states and battery charge. Connections and cable sizes are listed below.
View full screenRed = positive · dark = return. Crossings are not junctions. Read the assumptions before adapting a circuit.
What the pins on a rocker switch do
Count the terminals and look for a lamp symbol or numbers on the back. Carling's Contura switches, the pattern most marine and van panel switches copy, number them like this.
| Terminal | What it is | Connect it to |
|---|---|---|
| 1, 2, 3 | First pole: the common and the switched contacts | Fused supply to the common, load positive to the 'on' contact. The diagram on the switch shows which is which. |
| 4, 5, 6 | Second pole, on double-pole switches only | A second circuit that switches at the same time |
| 7 | Lamp negative (–) | The negative bus |
| 8 | Lamp positive (+) of an independent lamp | A separate fused supply, if the lamp should glow with the switch off |
| 9, 10 | More lamp terminals, on 10-terminal bodies | Follow the switch's own diagram |
Carling's datasheet lists terminals 1–3 for the first pole, 4–6 for the second, and 7–10 for lamps only; an independent lamp is wired 8 (+), 7 (–). Cheap unbranded switches do not always follow it: read the diagram printed on your switch or its packet before wiring.
Step by step
01
Isolate the battery
Switch the main battery switch off or take the fuse out of the slot you will use, so nothing is live while you crimp.
02
Run the fused feed to the switch
From a free fuse block slot, run a wire to the switch's supply terminal. The fuse protects this wire and the one after the switch, so pick it for the wire size, not just the load.
03
Run the switched wire to the load
From the switch's output terminal, run a wire of the same size to the load's positive. On the drawing that is 1.5 mm² for the lights and 2.5 mm² for the pump, sized for these lengths.
04
Return the negative to the bus
Take the load's negative straight back to the negative bus or the fuse block's negative stud, not through the switch.
05
Ground the lamp, if the switch has one
A lighted switch's lamp terminal (7 on a Contura) goes to negative. Without it the lamp has no return and stays dark, but the switch still works.
06
Test
Refit the fuse, switch on, and check the load runs and the lamp lights. With the switch off, measure 0 V at the load's positive.
Cable and fuse sizes
Sized by Crimp's ABYC E-11 based engine for the lengths shown. Lengths are one way; AWG is the approximate counterpart of the metric size.
| Connection | Length | Wire | Design current | Fuse | Drop |
|---|---|---|---|---|---|
| C1 · House battery + → Fuse block IN + | 50 cm1.6 ft | 2.5 mm²AWG 13 | 8 A | — | 0.22% |
| C2 · Fuse block 1 + → Rocker switch: lights A | 1 m3.3 ft | 1.5 mm²AWG 16 | 2 A | 3 A | 0.18% |
| C3 · Rocker switch: lights B → LED lights + | 3 m9.8 ft | 1.5 mm²AWG 16 | 2 A | — | 0.55% |
| C4 · LED lights − → Fuse block 1 − | 4 m13.1 ft | 1.5 mm²AWG 16 | 2 A | — | 0.73% |
| C5 · Fuse block 2 + → Rocker switch: pump A | 1 m3.3 ft | 2.5 mm²AWG 13 | 6 A | 7.5 A | 0.33% |
| C6 · Rocker switch: pump B → Water pump + | 2 m6.6 ft | 2.5 mm²AWG 13 | 6 A | — | 0.66% |
| C7 · Water pump − → Fuse block 2 − | 3 m9.8 ft | 2.5 mm²AWG 13 | 6 A | — | 0.98% |
| C8 · Fuse block IN − → House battery − | 50 cm1.6 ft | 2.5 mm²AWG 13 | 8 A | — | 0.22% |
A dash means the cable has no fuse of its own: a negative, a cable past a switch, or a run protected by the fuse upstream of it. Fuses on a battery post or in an inline holder are drawn on the diagram.
Common mistakes
Crimp's checks on this drawing: 0 critical, 2 to review. They stay visible when you open it.
- Switching the negative wire. The load then stays live when it is off, and a chafed wire can still short to ground.
- Leaving out the fuse because the switch has a light. The fuse protects the wire, not the switch.
- Feeding a high-current load through a small rocker. Above the switch's rating, switch a relay's coil instead.
- Joining the lamp terminal to the output. On some switches that makes the lamp a load across the supply, or keeps it lit all the time.
- Using solid wire behind a vibrating dash. Use stranded, tinned wire and crimped terminals.
- warning: No charging source
- info: Check fuse suitability: House battery
A planning example, not an installation certificate. Sizing follows Crimp's published method; check the manufacturer documents below for your exact parts.
Questions
How do I wire a 3-pin rocker switch?
A 3-pin on/off rocker is usually a single-pole switch with a lamp: one pin takes the fused supply, one goes to the load's positive and the third is the lamp's ground. Connect the ground pin to negative, or the lamp will not light. A 3-pin switch without a lamp is often an on/on or on/off/on switch instead, which feeds one of two loads; the diagram on the switch tells you which.
How do I wire a 5-pin rocker switch?
Most 5-pin panel rockers are a lighted on/off switch with two lamps: supply in, load out, a lamp ground and one or two lamp feeds, some used only for the 'on' light. The pin layout varies by maker, so follow the diagram printed on the switch. The power path is the same as any rocker: fused supply to the switch, switch to the load's positive, load's negative to the bus.
Does a rocker switch go on the positive or negative wire?
The positive. Switching the positive means the load and its wiring are dead when the switch is off. Switching the negative instead leaves the load and its positive wire live, so a chafed wire can still short to ground with the switch off.
What size fuse do I need for a rocker switch?
Pick the fuse for the wire the switch feeds, at or below that wire's rating, and at or below the switch's rating. In this drawing the 2 A LED lights get a 3 A fuse on 1.5 mm² wire and the 6 A pump gets 7.5 A on 2.5 mm². Open the drawing and change the lengths and loads; the sizes update.
Can I wire several switches from one fuse?
You can feed several switches from one fused supply, but then one fault blows everything on that fuse, and the fuse has to suit the smallest wire after it. One fuse per circuit, as in the drawing, is simpler to size and to fault-find.
When should I use a relay instead of just a rocker switch?
When the load draws more than the switch's rating, or the run to the dash is long. The rocker then only carries the relay coil's fraction of an amp, and the heavy current takes the short path from the battery to the load. See the 12V relay wiring diagram.