Current into a faulted string
(strings − 1) × 1.25 × Isc
Fault current from parallel strings against the panel's 15 A maximum series fuse| Strings | Fault current | Against 15 A |
|---|
| 2 | 7.33 A | No string fuses needed |
|---|
| 3 | 14.65 A | Under by only 0.35 A |
|---|
| 4 | 21.98 A | Fuse every string |
|---|
NEC 690.8 counts each string at 125 % of its short-circuit current, for sun brighter than the test standard. Many installers fuse every string from three strings up, whatever the arithmetic says.
Sizing a string fuse
The fuse must be at least 1.25 × 1.25 × Isc, so it does not blow in bright sun: 5.86 A × 1.56 = 9.2 A, so the next size up, 10 A. It must also be no larger than the panel's 15 A maximum series fuse.
Use fuses rated for PV (gPV) at the array's cold open-circuit voltage, in the positive of each string, or a combiner box that holds them. Automotive blade fuses are not rated to break a PV fault.
The battery side is a separate fuse: it protects the cable from the battery to the controller and its size comes from the controller's manual, 25–30 A for a Victron 100/20.