A separate inverter feed

Keep the inverter on its own heavy DC branch while solar charging and cabin lights share the same battery.

Red = positive · dark = return · crossings are not junctions. Full screen

Follow the circuit

  1. 01

    Keep the heavy branch short

    The inverter has its own positive and return cables. It does not draw power through the lighting branch or the solar controller's load terminals.

  2. 02

    Count the shared feeder

    The battery-to-bus cables also carry inverter current. Increasing only the final inverter cables leaves the common feeder unchanged.

  3. 03

    Separate cable protection from the inverter fuse

    The battery-end fuse protects the cable leaving the battery. The inverter's internal fuse has a different job and does not replace that decision.

The source and this example

Victron's Phoenix VE.Direct manual documents the battery connections and cable requirements for its 800 VA inverter.

We show the legacy 12/800 DC feed, small solar circuit and central ground bond. AC distribution, neutral bonding and the cabin earth electrode need a separate site design.

Before you build

  • Confirm the exact inverter generation: 800 VA / 650 W here, not the newer 800 W model.
  • Check surge demand, battery discharge capability, fuse behaviour and actual cable lengths.
  • Design the AC protection, earthing and neutral arrangement separately before connecting appliances.

This is a planning example. Cable sizing uses Crimp’s ABYC-based method; the drawing does not certify an installation.

Cable sizes and connections · 14 conductors

Lengths are one way. Sizes and currents come from the same Crimp model as the drawing. Each drop value covers one drawn conductor; the full circuit includes its supply and return. AWG values are approximate counterparts to the metric areas.

Cable table units
A separate inverter feed cable schedule
ConnectionLengthWireDesign currentFuseDrop
C1 · Victron 175W Mono +
→ Solar DP Isolator IN +
3 m2.5 mm²AWG 139 A—0.98%
C2 · Victron 175W Mono −
→ Solar DP Isolator IN −
3 m2.5 mm²AWG 139 A—0.98%
C3 · Solar DP Isolator OUT +
→ Victron MPPT 75/15 PV +
30 cm1.5 mm²AWG 169 A—0.16%
C4 · Solar DP Isolator OUT −
→ Victron MPPT 75/15 PV −
30 cm1.5 mm²AWG 169 A—0.16%
C5 · Victron MPPT 75/15 BATT +
→ Positive Bus Bar 1 +
1 m2.5 mm²AWG 1315 A20 A0.88%
C6 · Victron MPPT 75/15 BATT −
→ Negative Bus Bar 3 −
1 m2.5 mm²AWG 1315 A—0.88%
C7 · 200 Ah AGM bank +
→ Positive Bus Bar +
60 cm25 mm²AWG 462 A—0.22%
C8 · 200 Ah AGM bank −
→ Negative Bus Bar −
60 cm25 mm²AWG 462 A—0.22%
C9 · Positive Bus Bar 2 +
→ Cabin lighting · 2 A +
3 m1.5 mm²AWG 162 A3 A0.58%
C10 · Cabin lighting · 2 A −
→ Negative Bus Bar 2 −
3 m1.5 mm²AWG 162 A—0.58%
C11 · Positive Bus Bar 3 +
→ Victron Phoenix Inverter 12/800 DC +
80 cm25 mm²AWG 460 A100 A0.28%
C12 · Victron Phoenix Inverter 12/800 DC −
→ Negative Bus Bar 1 −
80 cm25 mm²AWG 460 A—0.28%
C13 · Victron Phoenix Inverter 12/800 Chassis PE −
→ Cabin earth connection 1 −
1 m16 mm²AWG 60 A—0.00%
C14 · Cabin earth connection −
→ 200 Ah AGM bank −
30 cm25 mm²AWG 40 A—0.00%

A dash means no fuse is assigned to that conductor; upstream protection may apply. Recheck the exact device, holder and placement after edits.

Equipment · 9 components
  • Victron 175W Mono

    19.4 V · 9.03 A rated / planning output · 175 W · 23.7 V STC Voc

    175W rigid mono panel, 12V nominal (Vmp 19.4V, Voc 23.7V) — works with PWM or MPPT controllers. 1485×668×30mm, 11kg, MC4 connectors.

  • Solar DP Isolator

    Illustrative two-pole PV disconnect. Select an actual DC-rated device for the array's cold open-circuit voltage and short-circuit current.

  • Victron MPPT 75/15

    15 A rated / planning output

    75/15 battery circuit: 20 A fuse, within Victron's 20–25 A range. The controller's LOAD terminals are unused; the lighting branch is battery-fed.

  • 200 Ah AGM bank

    12 V · 200 Ah

    40 A terminal fuse is this example's cable-protection choice. Verify the selected fuse, holder and interrupt capacity against the actual battery. Ah does not establish fault current.

  • Positive Bus Bar

    Positive bus bar — common feed with multiple output studs.

  • Cabin lighting · 2 A

    2 A load allowance · 24 W

    Generic 2 A lighting allowance. Replace it with the actual lamps and hours used before relying on the energy budget.

  • Negative Bus Bar

    Negative bus bar — common return with multiple output studs.

  • Victron Phoenix Inverter 12/800

    60 A load allowance · 650 W

    Legacy Phoenix 12/800: 800 VA / 650 W model. Dedicated DC branch; AC distribution and neutral bonding are outside this drawing. The chassis ground and battery-negative bond follow Wiring Unlimited section 7.7; the cabin earth electrode still needs site design. Battery-end fuse is an example cable-protection choice, not the internal inverter fuse.

  • Cabin earth connection

    Central grounding connection per Victron Wiring Unlimited section 7.7. Earth electrode, PV frame bonding and AC protection require the site-specific installation design.

Crimp checks · 2 findings to review

These are the current engine findings for the saved example. They remain visible when you open it in Crimp.

  • warning: Check fuse suitability: 200 Ah AGM bank
  • info: Check inverter disconnection